Please use this identifier to cite or link to this item: http://hdl.handle.net/2122/15973
Authors: Gambino, Salvatore* 
Falzone, Giuseppe* 
Ferro, Angelo* 
Laudani, Giuseppe* 
Scuderi, Luciano* 
Title: Tilt-Strain Changes Linked to a Jacking System Test
Journal: Civil and Environmental Engineering 
Series/Report no.: /18 (2022)
Publisher: Sciendo
Issue Date: 2022
DOI: 10.2478/cee-2022-0022
Abstract: A sector of the San Marco Hospital (Catania, Italy) was the subject of a jacking test in order to demonstrate the substitutability of the seismic isolator. A monitoring system, included tiltmeters and strain gauges, was applied to one column. Two distinct behaviours have been identified during the unloading stage, the first in which the column and the roof are still attached and a second in which the detachment takes place. The jacking system caused the column to return to its original position, induced by the building structure for thermoelastic causes.