Please use this identifier to cite or link to this item:
http://hdl.handle.net/2122/15973
Authors: | Gambino, Salvatore* Falzone, Giuseppe* Ferro, Angelo* Laudani, Giuseppe* Scuderi, Luciano* |
Title: | Tilt-Strain Changes Linked to a Jacking System Test | Journal: | Civil and Environmental Engineering | Series/Report no.: | /18 (2022) | Publisher: | Sciendo | Issue Date: | 2022 | DOI: | 10.2478/cee-2022-0022 | Abstract: | A sector of the San Marco Hospital (Catania, Italy) was the subject of a jacking test in order to demonstrate the substitutability of the seismic isolator. A monitoring system, included tiltmeters and strain gauges, was applied to one column. Two distinct behaviours have been identified during the unloading stage, the first in which the column and the roof are still attached and a second in which the detachment takes place. The jacking system caused the column to return to its original position, induced by the building structure for thermoelastic causes. |
Appears in Collections: | Article published / in press |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
2022 Gambino et al..pdf | Open Access Published Paper | 962.5 kB | Adobe PDF | View/Open |
Page view(s)
74
checked on Apr 17, 2024
Download(s)
30
checked on Apr 17, 2024